Description
Unipower HPL500-MB is equipped with a specially developed power supply for use from 100V - 575V - both single phased and three phased. Mains voltages in the whole world is hereby covered with one unit. HPL500-MB also measures currents up to 40A without the use of an external current converter.
As all Unipower HPL-modules the HPL500-MB integrates the functions necessary to establish an efficient and compact supervision or control; Start ti- mer, reaction timer, setpoints etc.
For setup simplicity the HPL500 includes peak detectors on the power measure- ment.
This MB-version is an RTU-slave on a MODbus network.
Technical Specifications
Mechanical spec.
Housing
Makrolon 8020 (30% GV), UL94V-1
(house).
Makrolon 2800, UL94V-2 (connector + front).
Mounting
Snap-on construction for 35mm DIN-rail or wall mounting.
Protection class
IP40 (house).
IP20 (connector).
Operating Temperature range:
-15 - +50 °C surrounding air.
Weight: Approx. 250g.
Dimensions: D 110 x W 56 x H 75 mm.
Terminal tight. torque: 7lbs/in, 0.79Nm Use 60/75 copper (CU) wire only
Electrical spec.
Supply / measuring voltage
1x100 - 1x400Vac ±10%.
3x100 - 3x575Vac ±10%
Current range
Internal: 0.5, 1, 2.5, 5, 10, 20, 30 & 40A
External: With N/5A converter (50-600A) Accuracy: Class 2.
Consumption: 2 VA
Frequency range 45 - 65 Hz
Relay spec. 250 VAC/5 Amp.
MODbus
RTU-slave
CE-mark to:
EN61326-1, EN61010-1
UL certified:
UL508, File E194022
GOST-R certified.