Unipower HPL110 Motor Load Monitor
Posted on 21st August 2019
THE CONCEPT
The Unipower HPL110 is a „low-cost“ member of a family of „Intelligent Power Control Units“. The unit measures true
power consumtption and shows the consumption as a percentage of the selected power-range. The power consumption (kW) is calculated from the following formula:
P = √3 x U x I x Cosϕ
The primary function of the HPL110 lies in the supervision and control of machinery driven by 3-phased AC-motors. The HPL110 integrates a Max. and/or a Min. kW limit detector plus the support functions necessary to establish the efficient and compact supervision or regulation of various types of machinery such as pumps, ventilators and conveyer belts. The HPL110 has a built in current converter that works up to 8 Amp.
Technical Specifications
Electrical
Voltage Range
See Technical info on the unit
Also availible:
3 x 120 VAC -> 3 x 575 VAC
Current Range
Internal: max. 8 Amp.
External: N/1 or N/5 converter.
Cosϕ ϕ Range: : 0-1
Frequency Range: 45-65 Hz.
Consumption.
Supply = measuring voltage, 2 VA.
Mechanical
Housing
Makrolon 8020 (30% GV), UL94V-1
(house).
Makrolon 2800, UL94V-2 (connector + front).
Mounting
Snap-on construction for 35mm DIN
rail mounting or panel mounting.
Protection Class
IP40 (house).
IP20 (connector).
Temperature Range: -15 - +50 oC
Weight: Approx. 400g.
Dimensions: D110 x W56 x H75 mm.
CE-mark to:
EN61326-1, EN61010-1
UL certified:
UL508, File E194022
Generally.
The power measurement principle is based upon integration of the power in every period (20 ms at 50Hz). Therefore the HPL110 also measures true power consumption on non sine shaped loads such as frequency inverters.
Programming:
The HPL110 is programmed by the use of only three keys located on the front panel. The „Mode“ key is used to select one of the seven programmable parameters. When a parameter is chosen the value may be altered by the use of the arrow keys.
Measurement ranges:
The HPL110 has a built-in current converter that works up to 8A. One of four internal current ranges may be chosen: 1, 3, 5 or 8A. If the unit measures on loads where the current exceeds 8A an external current converter must be connected. This is done by connecting the secondary side of the converter to pin
7 and 8 and choose the 1A or 5A currrent range, depending on the converter (N/1 or N/5). The measurement range in kW = √3 x U x I, where U is the nominal voltage and I is the choosen current range or nominal primary current of the external current converter. Ex. 1A and 400V gi- ves a measurement range of 0.692 kW corresponding to 100%.
Functions
The figure below shows a typical AC-motor power consumption curve (ex. pump) immediately after power has been applied to the motor. At the bottom of the figure a bar is shown indicating the position of the relay (On/ Off).
Choosing limits:
Deciding the limits can be done in two ways: Theoretically or using the peak detectors in the HPL110.
Theoretically:
Md = P2 x 60 / 2πn, where
Md: Torque where alarm should be given.
P2: Corresponding shaft power.
n: Revolutions in rev/min.
P1 = P2 + Po (Or from the efficiency curve of the motor).
Limit [%]= 100 x P1/P, where
P: Measurement range of the HPL110.
The limits can be deactivated by setting the Min limit to 0 and the Max limit to 101%. When a limit is deactivated „Off“ is written on the dis- play.
Peak detectors:
Leave the motor running at normal load and read the peak values by activating the arrow keys in kW[%] - mode. Place the Max limit appropriately above the Max peak value and the Min limit appropriately below the min peak value. The peak detectors may be reset seperately by pressing the relevant arrow key and at the same time activate the Reset key.
Ts: Start timer
The programmable start timer (Ts) is used to avoid alarms at motor start. The Ts delay function is activated after the power consumption reaches 5%. When Ts expires the limits, hys- teresis and Tr become active. If the power consumption drops below 5%, the supervision is switched off again.
Tr: Reaction timer
The figure shows how the reaction timer (Tr) is activated after the limit is exceeded. Tr is used to avoid alarms, unless the limit has been exceeded for a certain time. If Tr is set to 0, Tr equals the measurement interval of 20ms (16.7ms at 60Hz).
Resetting alarms:
Alarms may be reset by the reset key on the front panel or by Input S1.
Input S1: Auto or external reset
External reset: S1 is connected to Gnd by the use of a switch or optocoupler output See fig. 2.
Auto reset: If S1 is connected to Gnd, Auto reset mode is enabled, which leads to reset of alarms by hysteresis.
Hysteresis:
The figure to the left shows how possible Max and Min hysteresis bands are placed relatively to the limits. The hysteresis band always lies above a Min limit and below a Max limit. Hys- teresis is activated when an alarm is generated and the external reset is active (Input S1, Auto reset mode). If Auto reset is chosen and both limits are active, only the Max hysteresis band is active, because the HPL110 only has one relay.
Input S2: Blocking of alarms
Like Ts blocks for alarms during start of the motor, alarms can be ignored by setting S2 to Gnd.
Ex 1: If a brief overload is expected, a PLC output or the like may be used to block for a short period of time.
Ex 2: If the Min. kW limit is used, a spare break switch from the Motor Switch must be connected between the S2 input and Gnd, otherwise an alarm is generated each time the motor is switched off on purpose.
DIP switch:
The DIP switch is placed under the front plate (see figure 3).
SW1-No programming: The parameters may be read but not altered, when Sw 1 is On.
SW2: If this switch is on, no Min alarm will be given exceeding a Min limit if kW[%] < 5% before Tr expires.
Display & Programming Overview
The HPL110 is programmed by the use of only three keys located at the front panel. See paragraph about programming on page 2. The parameters and their programming ranges are listed in the table above. Parameters are stored in EEPROM. When no key has been activated for about 5 seconds the display returns to the kW[%] position. Note that the function of the keys is repeated if continuously activated.